Air Cooled Industrial Chillers
Product Details:
| Type | Chiller |
|---|---|
| Certification | CE |
| Place of Origin | Guangdong, China (Mainland) |
| Brand Name | ANGES |
| Model Number | HBC-3~HBC-10(D) |
Payment & Shipping Terms:
| Minimum Order Quantity: | 1 Set/Sets |
|---|---|
| Packaging Details: | Enclosed Wooden Cases |
| Payment Terms: | L/C,T/T |
| Supply Ability: | 300 Set/Sets per Month |
Detailed Product Description
HBC Series Environment-friendly Chillers use imported American hermetic scroll compressor--COPELAND.
Technical Parameter of HBC-3~HBC-10(D) Air Cooled Industrial Chillers
Model Item | HBC-3 | HBC-5 | HBC-6 | HBC-8(D) | HBC-10(D) | |
nominal cooling capacity | kcal/h | 6364 | 10630 | 12616 | 16374 | 21311 |
kw | 7.4 | 12.36 | 14.67 | 19.04 | 24.78 | |
input power | kw | 3.55 | 5.6 | 6.11 | 9.61 | 12 |
power supply | 3PH~380V 50HZ60HZ | |||||
refrigerant | type | R407c | ||||
type of control | capillary
| |||||
compressor | type | hermetic volution (piston) | ||||
power(kw) | 2.68 | 4.63 | 5.2 | 3.43*2 | 4.63*2 | |
condenser | type | finned copper tube + low noise outer rotor fan
| ||||
cooling air flow(m3/h) | 3000 | 5000 | 6000 | 8000 | 10000 | |
evaporator | type | water tank with coilshell and tube | ||||
chilled fluid flow(m3/h) | 1.27 | 2.13 | 2.52 | 3.27 | 4.26 | |
volume(L) | 50 | 70 | 70 | 120 | 200 | |
inlet and outlet pipe diameter (inch) | 1 | 1 | 1 | 1 | 1 | |
pump | power (kw) | 0.55 | 0.55 | 1.1 | 1.1 | 0.55 |
lift(m) | 25 | 25 | 25 | 25 | 25 | |
safety protection | compressor over temperature, over current, high and low pressure, over temperature,flow Switch, phase sequence, phase-missing, exhaust overheating, antifreezing | |||||
weight | kg | 175 | 180 | 310 | 450 | 175 |
dimension | mm | 930*520*975 | 1140*560*1040 | 1140*560*1040 | 1310*720*1270 | 1680*810*1280 |
Note: 1. nominal cooling capacity is according to: Inlet chilled fluid temperature: 12 Outlet chilled fluid temperature: 7 Inlet cooling air temperature: 30 Outlet cooling air temperature:35 2. working range: The temperature range of chilled fluid is from 5 to 35; Temperature difference between inlet and outlet chilled fluid is from 3 to 8. It is better to use the chiller while the ambient temperature at or below 35. We reserve the right to modify the above dimensions or parameters without further notice. | ||||||
Air Cooled Industrial Chillers
Other Products from this Supplier
See more
Air Cooled Industrial Chillers, air chiller, industrial chiller products from this supplier.
Product Showcase[30]
Products
- Air Cooled Screw Type Chillers [9]
- Water Cooled Screw Type Chillers [15]
- Environment-friendly Air Cooled Chillers [4]
- Environment-friendly Water Cooled Chillers [6]
- Air Cooled Industrial Water Chillers [8]
- Water Cooled Industrial Water Chillers [6]
- Laser Chillers [4]
- Cooling Tower [4]
- Mold Temperature Controller [4]
- Low Temperature Chillers [7]
- Oil Chillers [4]
- Heat and Cold Chillers [3]
- PCB chillers [4]
- Others [2]
Company Info
Shenzhen Anges Machinery Co., Ltd.
[China (Mainland)]
[Verified Member]
City: Shenzhen
Province/State: Guangdong
Country/Region : China (Mainland)
Business Type:Manufacturer
Online Postings: Products