Laser Cooling System (AL Series)
Product Details:
| Category | Industrial Chiller |
|---|---|
| Place of Origin | Guangdong, China |
| Brand Name | ANGES |
| Model Number | AL-12W ~AL-25W(D) |
Payment & Shipping Terms:
| Minimum Order Quantity: | 1 Set/Sets |
|---|---|
| Packaging Details: | Enclosed Plywood Cases |
| Payment Terms: | L/C,T/T |
| Supply Ability: | 300 Set/Sets per Month |
Detailed Product Description
The design of AL series Laser Chiller is on the basis of characteristic of laser equipments.
Technical Parameters of AL Series Laser Cooling System
Model Item | AL-12W | AL-15W(D) | AL-20W(D) | AL-25W(D) | ||||
nominal cooling capacity | kcal/h | 25146 | 35500 | 44230 | 50293 | |||
kw | 29.24 | 41.28 | 51.43 | 58.48 | ||||
input power | kw | 11.58 | 15.82 | 21 | 23.8 | |||
power supply | 3PH~380V 50HZ | |||||||
refrigerant | type | R22 | ||||||
type of control | thermostatic expansion valve | |||||||
compressor | type | hermetic scroll (piston) | ||||||
power(kw) | 2.8 | 4.66 | 5.2 | 3.8×2 | ||||
condenser | type | finned copper tube + low noise outer rotor fan | ||||||
cooling air flow (m3/h) | 12000 | 15000 | 20000 | 25000 | ||||
evaporator | type | water tank with coil | ||||||
chilled fluid flow(m3/h) | 5.03 | 7.1 | 8.84 | 10.06 | ||||
volume(L) | 200 | 270 | 350 | 350 | ||||
inlet and outlet pipe diameter (inch) | 1-1/2 | 2 | 2 | 2-1/2 | ||||
drain | 1/2 | |||||||
pump | power (kw) | 1.1 | 1.5 | 2.25 | 2.25 | |||
lift(m) | 25 | 26 | 28 | 28 | ||||
flow switch |
| |||||||
safety protection | compressor over temperature, over current, high and low pressure, over temperature,flow Switch, phase sequence, phase-missing, exhaust overheating, antifreezing | |||||||
weight | kg | 530 | 750 | 835 | 920 | |||
dimension | mm | 2000*1130*1914 | 1800*990*1680 | 2000*1130*1720 | 2000*1130*1914 | |||
Note: 1. nominal cooling capacity is according to: Inlet chilled fluid temperature: 12 Outlet chilled fluid temperature: 7 Inlet cooling air temperature: 30 Outlet cooling air temperature: 35 2. working range: The temperature range of chilled fluid is from 5 to 35; Temperature difference between inlet and outlet chilled fluid is from 3 to 8. The machine should be used when the ambient temperature at or below 35. We reserve the right to modify the above dimensions or parameters without further notice. | ||||||||
Laser Cooling System (AL Series)
Other Products from this Supplier
Product Showcase[30]
Products
- Air Cooled Screw Type Chillers [9]
- Water Cooled Screw Type Chillers [15]
- Environment-friendly Air Cooled Chillers [4]
- Environment-friendly Water Cooled Chillers [6]
- Air Cooled Industrial Water Chillers [8]
- Water Cooled Industrial Water Chillers [6]
- Laser Chillers [4]
- Cooling Tower [4]
- Mold Temperature Controller [4]
- Low Temperature Chillers [7]
- Oil Chillers [4]
- Heat and Cold Chillers [3]
- PCB chillers [4]
- Others [2]
Company Info
Shenzhen Anges Machinery Co., Ltd.
[China]
[Verified Member]
City: Shenzhen
Province/State: Guangdong
Country/Region : China
Business Type:Manufacturer
Online Postings: Products